Fan types and their subtypes are industry standard, recognized by all major fan producers.
Centrifugal Any of these fan subtypes can be built with long-lasting erosion-resistant liners. Airfoil (
Air foil) – Used for a wide range of applications in many industries, fans with hollow, airfoil-profiled blades are designed for use in airstreams where high efficiency and quiet operation are required. They are used extensively for continuous service at ambient and elevated temperatures in forced and induced draft applications in the metals, chemical, power generation, paper, rock products, glass,
resource recovery, incineration and other industries throughout the world.
Backward curve – These fans have efficiencies nearly as high as the airfoil design. An advantage is that their single-thickness, curved plate blades prevent the possibility of dust particle buildup inside the blade, as may occur with perforated airfoil blades. The robust design allows high tip-speed operation, and therefore this fan is often used in high-pressure applications.
Backward inclined – These fans have simple flat blades, backwardly inclined to match the velocity pattern of the air passing through the fan wheel for high-efficiency operation. These fans are typically used in high-volume, relatively low-pressure, clean air applications.
Radial blade – The flat blades of this type are arranged in a radial pattern. These rugged fans offer high pressure capability with average efficiency. They are often fitted with erosion-resistant liners to extend rotor life. The housing design is compact to minimize the floor space requirement.
Radial tipped – These fans have wheels that are backward curved, but in a way slightly different from backward curved fans. Backward curved fans have wheels whose blades curve outward, while radial-tip fans' blades are curved inward and radial at their tips (hence the name "radial tip"), while still in a backwardly-curved configuration. Their curvature can also be thought of as radial at the tips but gradually sloping toward the direction of rotation. This rugged design is used in high-volume flow rate applications when the pressure requirement is rather high and erosion resistance is necessary. It offers medium efficiencies. A common application is the dirty side of a baghouse or precipitator. The design is more compact than airfoil, backward curved or backward inclined fans.
Paddle-wheel – This is an open impeller design without shrouds. Although the efficiency is not high, this fan is well suited for applications with extremely high dust loading. It can be offered with field-replaceable blade liners from ceramic tiles or
tungsten carbide. This fan may also be used in high-temperature applications.
Forward-curve – This "squirrel cage" impeller generates the highest volume flow rate (for a given tip speed) of all the centrifugal fans. Therefore, it often has the advantage of offering the smallest physical package available for a given application. This type of fan is commonly used in high-temperature furnaces. However, these fans can only be used for conveying air with low dust loading because they are the most sensitive to particle build-up, but also due to the large number of blades that forward-curve wheels require.
Industrial exhausters – This is a relatively inexpensive, medium-duty, steeply inclined flat-bladed fan for exhausting gases, conveying chips, etc.
Pre-engineered fans (PE) – A series of fans of varying blade shapes that are usually available in only standard sizes. Because they are pre-engineered these fans may be available with relatively short delivery times. Often, pre-engineered rotors with various blade shapes may be installed into a common housing. These are often available in a wide range of volume and pressure requirements to meet the needs of many applications.
Pressure blowers – These are high-pressure, low-volume blowers used in combustion air applications in furnaces or to provide “blow-off” air for clearing and/or drying applications.
Surgeless blowers – These high-pressure, low-volume blowers have a reduced tendency for “surging” (periodic variation of flow rate) even at severely reduced fan speeds. This allows extreme turndown (low-flow) without significant pulsation.
Mechanical vapor recovery blowers -These specially designed centrifugal fans are designed to increase temperature and pressure of saturated steam in a closed-loop system.
Acid gas blowers - These very heavy construction blowers are suitable for inlet pressures from full vacuum to 100 psig. Materials are selected for corrosion resistance to the gases and particulate handled.
Specialty process gas blowers - These blowers are for high pressure petrochemical processes.
Axial High-temperature axial fans – These are high-volume fans designed to operate against low flow resistance in industrial convection furnaces. They may be of either single-direction or bi-directional designs. Extremely rugged, they are most often used in high-temperature furnace (up to 1800 degF) application.
Tube axial fans – These are axial fan units with fan wheels located in cylindrical tubes, without inlet or outlet dampers.
Vaneaxial fans – These axial flow fans have a higher pressure capability due to the presence of static vanes.
Variable pitch axial fans – The blades on these axial fans are manually adjustable to permit the blade angle to be changed. This allows operation over a much wider range of volume/pressure relationships. The blades are adjusted periodically to optimize efficiency by matching the blade pitch to the varying conditions for the application. These fans are often used in mining applications.
Variable pitch on-the-fly axial fans – These are similar to “Variable Pitch Axial Fans” except they include an internal mechanism that allows the blade pitch to be adjusted while the fan rotor is in motion. These versatile fans offer high-efficiency operation at many different points of operation. This instantaneous blade adjustment capability is an advantage that is possible with axial fans only.
Cooling fans - (also referred to as "cooling tower fans") - These are axial fans, typically with large diameters, for low pressures and large volumes of airflow. Applications are in wet mechanical cooling towers, air-cooled steam condensers, air-cooled heat exchangers, radiators, or similar air-cooled applications.
Mixed-flow fans - The gas flow patterns these fans produce resemble a combination of axial and centrifugal patterns, although the fan wheels often appear similar to centrifugal wheels. There are various types of mixed-flow fans, including gas-tight high-pressure fans and blowers.
Jet Jet Fans are used for daily ventilation requirements and smoke extraction in case of fire (250 ® C/120 min) These Industrial fans have symmetrical impeller blades; 100% reversible with low noise emissions IP55 motors, insulation class H (smoke extraction version). Application for Basement Ventilation & Tunnel Ventilation etc. ==Flow control==