(based on sea level).
Example Number 1: A tank with a liquid level 2 metres above the pump intake, plus the
atmospheric pressure of 10 metres, minus a 2 metre
friction loss into the pump (say for pipe & valve loss), minus the NPSH
R curve (say 2.5 metres) of the pre-designed pump (see the manufacturers curve) = an NPSH
A (available) of 7.5 metres. (not forgetting the flow duty). This equates to 3 times the NPSH required. This pump will operate well so long as all other parameters are correct. Remember that positive or negative flow duty will change the reading on the pump manufacture NPSH
R curve. The lower the flow, the lower the NPSH
R, and vice versa. Lifting out of a well will also create negative NPSH; however remember that atmospheric pressure at sea level is 10 metres! This helps us, as it gives us a bonus boost or “push” into the pump intake. (Remember that you only have 10 metres of atmospheric pressure as a bonus and nothing more!).
Example Number 2: A well or bore with an operating level of 5 metres below the intake, minus a 2 metre friction loss into pump (pipe loss), minus the NPSH
R curve (say 2.4 metres) of the pre-designed pump = an NPSH
A (available) of (negative) -9.4 metres. Adding the atmospheric pressure of 10 metres gives a positive NPSH
A of 0.6 metres. The minimum requirement is 0.6 metres above NPSH
R), so the pump should lift from the well. Using the situation from example 2 above, but pumping 70 degrees Celsius (158F) water from a hot spring, creating negative NPSH, yields the following:
Example Number 3: A well or bore running at 70 degrees Celsius (158F) with an operating level of 5 metres below the intake, minus a 2 metre friction loss into pump (pipe loss), minus the NPSH
R curve (say 2.4 metres) of the pre-designed pump, minus a temperature loss of 3 metres/10 feet = an NPSH
A (available) of (negative) -12.4 metres. Adding the atmospheric pressure of 10 metres and gives a negative NPSH
A of -2.4 metres remaining. Remembering that the minimum requirement is 600 mm above the NPSH
R therefore this pump will not be able to pump the 70 degree Celsius liquid and will cavitate and lose performance and cause damage. To work efficiently, the pump must be buried in the ground at a depth of 2.4 metres plus the required 600 mm minimum, totalling a total depth of 3 metres into the pit. (3.5 metres to be completely safe). A minimum of 600 mm (0.06 bar) and a recommended 1.5 metre (0.15
bar)
head pressure “higher” than the NPSH
R pressure value required by the manufacturer is required to allow the pump to operate properly. Serious damage may occur if a large pump has been sited incorrectly with an incorrect NPSH
R value and this may result in a very expensive pump or installation repair. NPSH problems may be able to be solved by changing the NPSH
R or by re-siting the pump. If an NPSH
A is say 10 bar then the pump you are using will deliver exactly 10 bar more over the entire operational curve of a pump than its listed operational curve. Example: A pump with a max. pressure head of 8 bar (80 metres) will actually run at 18 bar if the NPSH
A is 10 bar. i.e.: 8 bar (pump curve) plus 10 bar NPSH
A = 18 bar. This
phenomenon is what manufacturers use when they design
multistage pumps, (Pumps with more than one impeller). Each multi stacked impeller boosts the succeeding impeller to raise the pressure head. Some pumps can have up to 150 stages or more, in order to boost heads up to hundreds of metres. == References ==