The relationship between real power and apparent power is described by the
power factor. With a purely resistive load, they are the same: the apparent power is equal to the real power. Where a reactive (capacitive or inductive) component is present in the load, the apparent power is greater than the real power as voltage and current are no longer in phase. In the limiting case of a purely reactive load, current is drawn but no power is dissipated in the load. Some devices, including
uninterruptible power supplies (UPSs), have ratings both for maximum volt-amperes and maximum watts. A common
prefixed derived unit is "kilovolt-ampere" (symbol kVA). The VA rating is limited by the maximum permissible current, and the watt rating by the power-handling capacity of the device. When a UPS powers equipment which presents a
reactive load with a low power factor, neither limit may safely be exceeded. For example, a (large) UPS system rated to deliver 400,000 volt-amperes (400 kVA) at 220 volts can deliver a current of 1818 amperes (these are RMS values). VA ratings are also often used for transformers; maximum output current is then VA rating divided by nominal output voltage. Transformers with the same sized core usually have the same VA rating. The convention of using the volt-ampere to distinguish apparent power from real power is allowed by the SI standard. == Volt-ampere reactive ==