A set of three water pressure measurements are recorded from two hydrants. One hydrant is known as the residual hydrant or test hydrant and is located on or near the water main where a new water connection is desired. From this test hydrant, a
static pressure and a residual pressure will be measured. The other hydrant, known as the flow hydrant, is usually the nearest hydrant away from the test hydrant. The flow hydrant is fitted with a diffuser device containing a
pitot tube that measures
stagnation pressure in the middle of the stream while the hydrant is flowing. First, a static pressure gauge is attached to the test hydrant and the static water pressure is measured at the test hydrant. Second, the flow hydrant opened to allow water to flow in a fully open condition. Simultaneously the pitot tube pressure is recorded from the flow hydrant while the residual pressure is measured from the test hydrant. These three pressures, the static pressure, the stagnation pressure, and the residual pressure, along with a specified design pressure of 20psi taken from the American Water Works Association (AWWA) or the NFPA are input into the
Hazen-Williams formula to calculate the available flow for fire protection. ==The residual flow formula==