IEC 60870-5-101 [IEC101] is a standard for power system monitoring, control & associated communications for telecontrol, teleprotection, and associated telecommunications for electric power systems. This is completely compatible with IEC 60870-5-1 to IEC 60870-5-5 standards and uses standard asynchronous serial tele-control channel interface between
DTE and
DCE. The standard is suitable for multiple configurations like point-to-point, star, multidrop etc.
Features • Supports unbalanced (only master initiated message) & balanced (can be master/slave initiated) modes of data transfer. • Link address and
ASDU (Application Service Data Unit) addresses are provided for classifying the
end station and different segments under the same. • Data is classified into different information objects and each information object is provided with a specific address. • Facility to classify the data into high priority (class-1) and low priority (class-2) and transfer the same using separate mechanisms. • Possibility of classifying the data into different groups (1-16) to get the data according to the group by issuing specific group interrogation commands from the master & obtaining data under all the groups by issuing a general interrogation. • Cyclic & Spontaneous data updating schemes are provided. • Facility for time synchronization • Schemes for transfer of files-Example:IED's will store disturbance recorder file in the memory, When electrical disturbance is occurred in the field. This file can be retrieved through IEC103 protocol for fault analysis
Frame format The character format of IEC 101 uses 1 bit each for start, stop and parity, as well as 8 data bits. FT1.2 (defined in IEC 60870-5-1) is used for frame format of IEC 101 which is suitable for
asynchronous serial communication with
Hamming distance of 4. This uses 3 types of frame formats -
Frame with variable length ASDU,
Frame with fixed length &
single character. Single character is used for acknowledgments, fixed length frames are used for commands & variable lengths are used for sending data. The details of variable length frame is given below
Types supported • Single indication without / with 24 / with 56 bit timestamps. • Double indication without / with 24 / with 56 bit timestamps. • Step position information without / with 24 / with 56 bit timestamps. • Measured value – normalized, scaled, short floating point without / with timestamps. • Bitstring of 32 bit without / with timestamps. • Integrated totals (counters) without / with timestamps. • Packed events (start & tripping ) of protection equipments • Single commands • Double commands • Regulating step command • Set point commands of various data formats • Bitstring commands • Interrogation commands • Clock synchronization & delay acquisition commands • Test & reset commands -- ==IEC 60870-5-103==