Cooling performance is typically expressed in units of BTU/hr/watt as the
energy efficiency ratio (EER), while heating performance is typically reduced to dimensionless units as the
coefficient of performance (COP). The conversion factor is 3.41 BTU/hr/watt. Since a heat pump moves three to five times more heat energy than the electric energy it consumes, the total energy output is much greater than the electrical input. This results in net thermal efficiencies greater than 300% as compared to radiant electric heat being 100% efficient. Traditional combustion furnaces and
electric heaters can never exceed 100% efficiency. Ground source heat pumps can reduce energy consumption – and corresponding air pollution emissions – up to 72% compared to electric resistance heating with standard air-conditioning equipment. Efficient compressors, variable speed compressors and larger heat exchangers all contribute to heat pump efficiency. Residential ground source heat pumps on the market today have standard COPs ranging from 2.4 to 5.0 and EERs ranging from 10.6 to 30. To qualify for an
Energy Star label, heat pumps must meet certain minimum COP and EER ratings which depend on the ground heat exchanger type. For closed-loop systems, the ISO 13256-1 heating COP must be 3.3 or greater and the cooling EER must be 14.1 or greater. Standards ARI 210 and 240 define
Seasonal Energy Efficiency Ratio (SEER) and
Heating Seasonal Performance Factors (HSPF) to account for the impact of seasonal variations on air source heat pumps. These numbers are normally not applicable and should not be compared to ground source heat pump ratings. However,
Natural Resources Canada has adapted this approach to calculate typical seasonally adjusted HSPFs for ground-source heat pumps in Canada. The NRC HSPFs ranged from 8.7 to 12.8 BTU/hr/watt (2.6 to 3.8 in nondimensional factors, or 255% to 375% seasonal average electricity utilization efficiency) for the most populated regions of Canada. For the sake of comparing heat pump appliances to each other, independently from other system components, a few standard test conditions have been established by the
American Refrigerant Institute (ARI) and more recently by the
International Organization for Standardization. Standard ARI 330 ratings were intended for closed-loop ground-source heat pumps, and assume secondary loop water temperatures of for air conditioning and for heating. These temperatures are typical of installations in the northern US. Standard ARI 325 ratings were intended for open-loop ground-source heat pumps, and include two sets of ratings for groundwater temperatures of and . ARI 325 budgets more electricity for water pumping than ARI 330. Neither of these standards attempts to account for seasonal variations. Standard ARI 870 ratings are intended for direct exchange ground-source heat pumps.
ASHRAE transitioned to ISO 13256–1 in 2001, which replaces ARI 320, 325 and 330. The new ISO standard produces slightly higher ratings because it no longer budgets any electricity for water pumps. is the diversity of the time and space scales involved. Four space scales and eight time scales are involved in the heat transfer of GHEs. The first space scale having practical importance is the diameter of the borehole (~ 0.1 m) and the associated time is on the order of 1 hr, during which the effect of the heat capacity of the backfilling material is significant. The second important space dimension is the half distance between two adjacent boreholes, which is on the order of several meters. The corresponding time is on the order of a month, during which the thermal interaction between adjacent boreholes is important. The largest space scale can be tens of meters or more, such as the half-length of a borehole and the horizontal scale of a GHE cluster. The time scale involved is as long as the lifetime of a GHE (decades). The short-term hourly temperature response of the ground is vital for analyzing the energy of ground-source heat pump systems and for their optimum control and operation. By contrast, the long-term response determines the overall feasibility of a system from the standpoint of the life cycle. The main questions that engineers may ask in the early stages of designing a GHE are (a) what the heat transfer rate of a GHE as a function of time is, given a particular temperature difference between the circulating fluid and the ground, and (b) what the temperature difference as a function of time is, given a required heat exchange rate. In the language of heat transfer, the two questions can probably be expressed as q_l = [T_f(t) - T_0]/R(t) where
Tf is the average temperature of the circulating fluid,
T0 is the effective, undisturbed temperature of the ground,
ql is the heat transfer rate of the GHE per unit time per unit length (W/m), and
R is the total thermal resistance (m
.K/W).
R(
t) is often an unknown variable that needs to be determined by heat transfer analysis. Despite
R(
t) being a function of time, analytical models exclusively decompose it into a time-independent part and a time-dependent part to simplify the analysis. Various models for the time-independent and time-dependent R can be found in the references. Heat captured and stored in thermal banks in the summer can be retrieved efficiently in the winter. Heat storage efficiency increases with scale, so this advantage is most significant in commercial or
district heating systems.
Geosolar combisystems have been used to heat and cool a greenhouse using an
aquifer for thermal storage. In summer, the greenhouse is cooled with cold ground water. This heats the water in the aquifer which can become a warm source for heating in winter. The combination of cold and heat storage with heat pumps can be combined with water/humidity regulation. These principles are used to provide
renewable heat and renewable cooling to all kinds of buildings. Also the efficiency of existing small heat pump installations can be improved by adding large, cheap, water-filled solar collectors. These may be integrated into a to-be-overhauled parking lot, or in walls or roof constructions by installing one-inch
PE pipes into the outer layer. ==Environmental impact==