In the
nuclear plant field,
steam generator refers to a specific type of large
heat exchanger used in a
pressurized water reactor (PWR) to thermally connect the primary (reactor plant) and secondary (steam plant) systems, which generates steam. In a
boiling water reactor (BWR), no separate steam generator is used and water boils in the reactor core. In some industrial settings, there can also be steam-producing heat exchangers called
heat recovery steam generators (HRSG) which utilize heat from some industrial process, most commonly utilizing hot exhaust from a gas turbine. The steam generating boiler has to produce steam at the high purity, pressure and temperature required for the steam turbine that drives the electrical generator.
Geothermal plants do not need boilers because they use naturally occurring steam sources. Heat exchangers may be used where the geothermal steam is very corrosive or contains excessive suspended solids. A fossil fuel steam generator includes an
economizer, a
steam drum, and the
furnace with its steam generating tubes and superheater coils. Necessary
safety valves are located at suitable points to protect against excessive boiler pressure. The air and
flue gas path equipment include: forced draft (FD)
fan,
air preheater (AP), boiler furnace, induced draft (ID) fan, fly ash collectors (
electrostatic precipitator or
baghouse), and the
flue-gas stack.
Feed water heating The boiler feed water used in the
steam boiler is a means of transferring heat energy from the burning fuel to the mechanical energy of the spinning
steam turbine. The total feed water consists of recirculated
condensate water and purified
makeup water. Because the metallic materials it contacts are subject to
corrosion at high temperatures and pressures, the makeup water is highly purified before use. A system of
water softeners and
ion exchange demineralizes produces water so pure that it coincidentally becomes an electrical
insulator, with
conductivity in the range of 0.3–1.0
microsiemens per centimeter. The makeup water in a 500 MWe plant amounts to perhaps 120 US gallons per minute (7.6 L/s) to replace water drawn off from the boiler drums for water purity management, and to also offset the small losses from steam leaks in the system. The feed water cycle begins with condensate water being pumped out of the
condenser after traveling through the steam turbines. The condensate flow rate at full load in a 500 MW plant is about 6,000 US gallons per minute (400 L/s). The water is usually pressurized in two stages, and typically flows through a series of six or seven intermediate feed water heaters, heated up at each point with steam extracted from an appropriate extraction connection on the turbines and gaining temperature at each stage. Typically, in the middle of this series of feedwater heaters, and before the second stage of pressurization, the condensate plus the makeup water flows through a
deaerator that removes dissolved air from the water, further purifying and reducing its corrosiveness. The water may be dosed following this point with
hydrazine, a chemical that removes the remaining
oxygen in the water to below 5
parts per billion (ppb). It is also dosed with
pH control agents such as
ammonia or
morpholine to keep the residual
acidity low and thus non-corrosive.
Boiler operation The boiler is a rectangular
furnace about on a side and tall. Its walls are made of a web of high pressure steel tubes about in diameter. Fuel such as
pulverized coal is air-blown into the furnace through burners located at the four corners, or along one wall, or two opposite walls, and it is ignited to rapidly burn, forming a large fireball at the center. The
thermal radiation of the fireball heats the water that circulates through the boiler tubes near the boiler perimeter. The water circulation rate in the boiler is three to four times the throughput. As the water in the
boiler circulates it absorbs heat and changes into steam. It is separated from the water inside a drum at the top of the furnace. The saturated steam is introduced into
superheat pendant tubes that hang in the hottest part of the combustion gases as they exit the furnace. Here the steam is superheated to to prepare it for the turbine. Plants that use gas turbines to heat the water for conversion into steam use boilers known as
heat recovery steam generators (HRSG). The exhaust heat from the gas turbines is used to make superheated steam that is then used in a conventional water-steam generation cycle, as described in the
gas turbine combined-cycle plants section.
Boiler furnace and steam drum The water enters the boiler through a section in the convection pass called the
economizer. From the economizer it passes to the
steam drum and from there it goes through downcomers to inlet headers at the bottom of the water walls. From these headers the water rises through the water walls of the furnace where some of it is turned into steam and the mixture of water and steam then re-enters the steam drum. This process may be driven purely by
natural circulation (because the water is the downcomers is denser than the water/steam mixture in the water walls) or assisted by pumps. In the steam drum, the water is returned to the downcomers and the steam is passed through a series of
steam separators and dryers that remove water droplets from the steam. The dry steam then flows into the superheater coils. The boiler furnace auxiliary equipment includes
coal feed nozzles and igniter guns,
soot blowers, water lancing, and observation ports (in the furnace walls) for observation of the furnace interior. Furnace
explosions due to any accumulation of combustible gases after a trip-out are avoided by flushing out such gases from the combustion zone before igniting the coal. The steam drum (as well as the
superheater coils and headers) have air vents and drains needed for initial start up.
Superheater Fossil fuel power stations often have a
superheater section in the steam generating furnace. The steam passes through drying equipment inside the steam drum on to the superheater, a set of tubes in the furnace. Here the steam picks up more energy from hot flue gases outside the tubing, and its temperature is now superheated above the saturation temperature. The superheated steam is then piped through the main steam lines to the valves before the high-pressure turbine. Nuclear-powered steam plants do not have such sections but produce steam at essentially saturated conditions. Experimental nuclear plants were equipped with fossil-fired superheaters in an attempt to improve overall plant operating cost.
Steam condensing The condenser condenses the steam from the exhaust of the turbine into liquid to allow it to be pumped. If the condenser can be made cooler, the pressure of the exhaust steam is reduced and efficiency of the
cycle increases. The surface condenser is a
shell and tube heat exchanger in which cooling water is circulated through the tubes. The exhaust steam from the low-pressure turbine enters the shell, where it is cooled and converted to condensate (water) by flowing over the tubes as shown in the adjacent diagram. Such condensers use
steam ejectors or
rotary motor-driven exhausts for continuous removal of air and gases from the steam side to maintain
vacuum. For best efficiency, the temperature in the condenser must be kept as low as practical in order to achieve the lowest possible pressure in the condensing steam. Since the condenser temperature can almost always be kept significantly below 100 °C where the
vapor pressure of water is much less than atmospheric pressure, the condenser generally works under
vacuum. Thus leaks of non-condensible air into the closed loop must be prevented. Typically the cooling water causes the steam to condense at a temperature of about and that creates an
absolute pressure in the condenser of about , i.e. a
vacuum of about relative to atmospheric pressure. The large decrease in volume that occurs when water vapor condenses to liquid creates the vacuum that generally increases the efficiency of the turbines. The limiting factor is the temperature of the cooling water. That is limited by the prevailing average climatic conditions at the power station's location. It may be possible to lower the temperature beyond the turbine limits during winter, causing excessive condensation in the turbine. Plants operating in hot climates may have to reduce output if their source of condenser cooling water becomes warmer. Unfortunately this usually coincides with periods of high electrical demand for
air conditioning. The condenser generally uses either circulating cooling water from a
cooling tower to reject waste heat to the atmosphere, or
once-through cooling (OTC) water from a river, lake or ocean. In the United States, about two-thirds of power plants use OTC systems, which often have significant adverse environmental impacts. The impacts include
thermal pollution and killing large numbers of fish and other aquatic species at
cooling water intakes. The heat absorbed by the circulating cooling water in the condenser tubes must also be removed to maintain the ability of the water to cool as it circulates. This is done by pumping the warm water from the condenser through either natural draft, forced draft or induced draft
cooling towers (as seen in the adjacent image) that reduce the temperature of the water by evaporation, by about —expelling
waste heat to the atmosphere. The circulation flow rate of the cooling water in a 500
MW unit is about 14.2 m3/s (500 ft3/s or 225,000 US gal/min) at full load. The condenser tubes are typically made
stainless steel or other alloys to resist corrosion from either side. Nevertheless, they may become internally fouled during operation by bacteria or algae in the cooling water or by mineral scaling, all of which inhibit heat transfer and reduce
thermodynamic efficiency. Many plants include an automatic cleaning system that circulates sponge rubber balls through the tubes to scrub them clean without the need to take the system off-line. The cooling water used to condense the steam in the condenser returns to its source without having been changed other than having been warmed. If the water returns to a local water body (rather than a circulating cooling tower), it is often tempered with cool 'raw' water to prevent thermal shock when discharged into that body of water. Another form of condensing system is the
air-cooled condenser. The process is similar to that of a
radiator and fan. Exhaust heat from the low-pressure section of a steam turbine runs through the condensing tubes, the tubes are usually finned and ambient air is pushed through the fins with the help of a large fan. The steam condenses to water to be reused in the water-steam cycle. Air-cooled condensers typically operate at a higher temperature than water-cooled versions. While saving water, the efficiency of the cycle is reduced (resulting in more carbon dioxide per megawatt-hour of electricity). From the bottom of the condenser, powerful
condensate pumps recycle the condensed steam (water) back to the water/steam cycle.
Reheater Power station furnaces may have a reheater section containing tubes heated by hot flue gases outside the tubes. Exhaust steam from the high-pressure turbine is passed through these heated tubes to collect more energy before driving the intermediate and then low-pressure turbines.
Air path External fans are provided to give sufficient air for combustion. The Primary air fan takes air from the atmosphere and, first warms the air in the air preheater for better economy. Primary air then passes through the coal pulverizers, and carries the coal dust to the burners for injection into the furnace. The Secondary air fan takes air from the atmosphere and, first warms the air in the air preheater for better economy. Secondary air is mixed with the coal/primary air flow in the burners. The induced draft fan assists the FD fan by drawing out combustible gases from the furnace, maintaining slightly below atmospheric pressure in the furnace to avoid leakage of combustion products from the boiler casing. ==Steam turbine generator==